Timeout für Boilerlegioschaltung hinzugefühgt.
This commit is contained in:
@@ -185,6 +185,9 @@ class Boiler_2_Stufig_Mit_Fueler extends IPSModule
|
|||||||
if ($LegioCounter > 120960 && $this->ist_nachts()) {
|
if ($LegioCounter > 120960 && $this->ist_nachts()) {
|
||||||
$minTemp = $LegioTemp;
|
$minTemp = $LegioTemp;
|
||||||
}
|
}
|
||||||
|
if ($LegioCounter > 138240) { // Timeout für Legio wenn temperatur nicht erreicht werden kann, setze legionellenfunktion zurück
|
||||||
|
$LegioCounter = 0;
|
||||||
|
}
|
||||||
|
|
||||||
$this->SetValue("LegioCounter", $LegioCounter);
|
$this->SetValue("LegioCounter", $LegioCounter);
|
||||||
|
|
||||||
|
|||||||
@@ -6,7 +6,7 @@
|
|||||||
"compatibility": {
|
"compatibility": {
|
||||||
"version": "7.1"
|
"version": "7.1"
|
||||||
},
|
},
|
||||||
"version": "0.293",
|
"version": "0.294",
|
||||||
|
|
||||||
"build": 0,
|
"build": 0,
|
||||||
"date": 0
|
"date": 0
|
||||||
|
|||||||