# Separate physical load / EV-SDL observation (NO dispatch or training permission)
|
|
|
|
## Implemented 2026-10-02
|
|
|
|
- `NetzfahrplanV4Messsicht` recalculates independent physical-load, physical-storage,
|
|
unfiltered modelled allocation and SolarEdge-origin views from explicitly identified
|
|
raw snapshots. Quality failures in held virtual accounts do not veto otherwise
|
|
consistent physical inputs. Missing/stale physical inputs still invalidate their
|
|
respective view. No automatic relaxation of age/skew limits.
|
|
- EV/SDL model: delta = physical - requestedEV - requestedSDL; distribute delta in
|
|
proportion to the absolute requested powers. The SDL component is obtained from
|
|
physical minus modelled EV to preserve numerical closure. This is an accounting
|
|
convention, NOT independently measured EV and SDL and NOT a verified response.
|
|
- Command changes more recent than the oldest physical feedback are flagged. Unknown
|
|
change timestamps, tracking mismatch, aged/missing origins and idle unallocated
|
|
power remain explicit. There is no held-value filter and no forced convergence of
|
|
displayed power to the requested value. All proposals keep `canDispatch=false`.
|
|
- Actual legacy filter outputs are displayed solely for comparison. They are not
|
|
reused as inputs of physical-load or unfiltered partition calculations. No changes
|
|
to the legacy filter, physical driver, EV/SDL setpoints, SOC integration or accounts.
|
|
|
|
## New read-only origin finding
|
|
|
|
Selected event 38921 writes legacy PV variable 20335 using:
|
|
|
|
a = 10 ** GetValue(41853) * GetValue(37975) + GetValue(21447)
|
|
if (a < 0) a = 0
|
|
SetValue(20335, a)
|
|
|
|
Arithmetic statements were inspected without exposing arbitrary scripts/credentials.
|
|
Verified saved configuration: variable 37975 parent 35514, register 40083; scale
|
|
41853 parent 48996, register 40084; battery 21447 parent 30789. An independently
|
|
updated 20335 is therefore not an independent PV reading and cannot certify all
|
|
input timestamps. A second constrained arithmetic read confirmed the condition
|
|
`if ($a < 0)`; this clamp applies to the legacy calculated PV value, not to the
|
|
new signed terminal-power observation. Neither proves the full AC/DC boundary.
|
|
|
|
The staged observer additionally records the ORIGINAL mantissa and exponent, not
|
|
only their periodically rewritten derived PV result. The alternative candidate
|
|
uses the scaled terminal power ONCE for this inverter (removing its derived-PV
|
|
and battery terms). GoodWe AC/DC boundaries and full-site physical boundary are
|
|
still unverified. This is not a definitive corrected house meter or live forecast.
|
|
|
|
## Standalone installation / operational scope
|
|
|
|
Stage on test host: `/srv/agent/netplan-v4-separated-observer-stage`.
|
|
User invocation inside Symcon only:
|
|
|
|
require '/srv/agent/netplan-v4-separated-observer-stage/install.php';
|
|
|
|
Creates only a NEW root category, three textual diagnostic variables, observe and
|
|
stop scripts and a NEW 30-second timer. Reads 23 existing numeric variables twice;
|
|
no Modbus polling requests, network calls, archive settings, existing module or
|
|
control timer updates. Existing 21-channel raw collector continues untouched.
|
|
|
|
New daily journals contain the selected numeric raw snapshot and derived views.
|
|
A new immutable mapping/inventory reference binds the corrected user EV allocation
|
|
161.44 kWh / 39 kW. Original collector metadata and its correction addendum remain
|
|
unchanged. No rescaling or resetting of virtual SOC/energy accounts.
|
|
|
|
Derived journal and LATEST/STATUS reports are 0644 WITHIN mode-0700 private stage
|
|
and data directories, allowing the authorized agent to inspect these selected
|
|
new outputs without repeated manual exports. No permissions on original journals,
|
|
Symcon directories or unrelated data are changed. Quotas reuse 64 MiB/day, 512 MiB
|
|
in total and 100 MiB disk reserve; exceeding them stops recording visibly and does
|
|
not delete old data. No network transfer or cloud trainer is activated.
|
|
|
|
## Validation and limitations
|
|
|
|
40 pure view checks + 32 native-mock checks passed on PHP 8.3 CLI at test host.
|
|
Regression: 36 raw-capture + 19 native-capture + 34 accounting checks passed with
|
|
new additive `raw_power`/`scale` units. Total 161 isolated checks. Full relevant PHP
|
|
source lint passed. Not a full PHPUnit run, Symcon kernel trial or hardware test.
|
|
|
|
Tests cover opposite EV/SDL requests, held output, non-unique partition labelling,
|
|
negative terminal power, scale/sentinel validity, old dependency timestamps, changed
|
|
commands, missing source, no duplicate native objects, unchanged existing signals,
|
|
append preservation, source drift, private output restrictions and stop behavior.
|
|
|
|
The observer is PREPARED, not started by the assistant. It does not replace the
|
|
installed receiver or its existing preview calculation. The preview/driver must
|
|
only be switched after measurement-boundary and feedback policy acceptance. Model
|
|
training and five-minute reconstruction must consume the new versioned snapshots
|
|
separately; there is no training eligibility or zero future-SDL assumption here.
|
|
|
|
Device-side command-loss protection and exact model/firmware identification remain
|
|
open. Official SolarEdge PDF fetch was unavailable (403/error); no device-specific
|
|
register suitability or watchdog behavior was inferred from a third-party source.
|